Requirement
PURPOSE
Ensure HVAC systems are providing airflow rates as designed.
CRITERIA
Retain an independent, third-party testing agent to perform a test and balance of the system’s airflow distribution for all field-installed ductwork. The test and balance report must follow equipment test sheets and communicate required data per Associated Air Balance Council (AABC) or National Environmental Balancing Bureau (NEBB). The third party must be an AABC or NEBB certified organization.
Demonstrate that air system is balanced to within +/- 10% of the Design Air Flow Values at each register per the Test and Balance report.
Refer to ES R5: Duct System Requirements for a complete list of ductwork requirements.
At minimum, the report should include the following Design and Actual values:
- Supply airflow for each air handling unit and each register
- Return airflow for each air handling unit and each register
- Outside airflow for each air handling device
- Percent difference for each of the above measurements
- Exhaust rates per fan and each register (including all hoods and make-up air)
- Minimum and maximum airflows for terminal units
Ductless Mechanical Systems
Ductless heating/cooling equipment does not need to be tested, adjusted or balanced by a third-party test and balance technician. However, all projects must receive a test and balance report to ensure that exhaust and outside air flow rates comply with the design.
VERIFICATION
- Provide third party test and balance report
RESOURCES
Associated Air Balance Council www.aabc.com
National Environmental Balancing Bureau www.nebb.org
Comments
0 comments
Please sign in to leave a comment.