(4 credits)
Aim
To reduce operational energy consumption and associated carbon emissions by installing appropriate controls to reduce unnecessary energy consumption (waste).
Question
- Are there internal temperature controllers in individual rooms or zones?
- Can the output from the heat generator and cooling generator be modulated?
- Does the system have an interlock control?
- Can the air flow be controlled at room level?
- Is the supply air temperature controlled?
- Is the air humidity controlled?
Credits | Question | Select a single answer | Points awarded | Points available |
* | 1 | Asset does not have both heating and cooling | Filtered | 0 |
Yes, with communication between controllers | 3 | 3 | ||
Yes, by thermostatic values or an electronic controller | 2 | 3 | ||
No | 0 | 3 | ||
* | 2 | Asset does not have both heating and cooling | Filtered | 0 |
Indoor temperature control | 3 | 3 | ||
Outside temperature compensation control | 2 | 3 | ||
No control | 0 | 3 | ||
* | 3 | Asset does not have both heating and cooling | Filtered | 0 |
Total interlock | 3 | 3 | ||
Partial interlock | 2 | 3 | ||
No interlock | 0 | 3 | ||
* | 4 | No mechanical ventilation or heating or cooling distributed by air | Filtered | 0 |
Demand or presence dependent air flow control at room level | 3 | 3 | ||
Time dependent air flow control at room level | 2 | 3 | ||
No air flow control at room level | 0 | 3 | ||
* | 5 | No heating or cooling distributed by air | Filtered | 0 |
Variable set point with load compensation of supply air temperature | 3 | 3 | ||
Variable set point with outdoor temperature compensation of supply air temperature | 2 | 3 | ||
Constant set point for supply air temperature | 1 | 3 | ||
No control of air supply temperature | 0 | 3 | ||
* | 6 | No humidification provided in the asset | Filtered | 0 |
Room or exhaust or supply air humidity control | 3 | 3 | ||
Supply air humidity limitation | 2 | 3 | ||
No air humidity control | 0 | 3 |
Methodology
Credit allocation
Credits are based on the percentage of points achieved against number of points available as follows;
Table 19: Allocation of credits
Percentage of available points achieved | Credits |
≥ 20% | 1 |
≥ 40% | 2 |
≥ 60% | 3 |
≥ 80% | 4 |
Evidence
Criteria | Evidence requirement |
- | The evidence below is not exhaustive, please also refer to the ‘BREEAM evidential requirements’ section in the scope of the Guidance for appropriate evidence types which can be used to demonstrate compliance. |
All | Visual inspection and verification through photographic evidence of controls. |
All | All remote control must be via an accessible device. |
All | Extract of relevant O&M manuals or copy of manufacturer information. |
Definitions
Appropriate controls:
These include separate or integrated controls associated with individual building servicing systems and appliances as well as building management system (BMS) and remote-control devices e.g., via a smartphone app.
Interlock control:
This control prevents the heating system operating when the cooling system is operating and vice versa.
Accessible device:
Devices are accessible if they link with a web or mobile interface that meet the WCAG2.0 (ISO/IEC 40500) accessibility standards (www.w3.org;www.iso.org).
Where the above is not met, (e.g. only a visual display unit is installed), a device must have been installed that meets an equivalent level of accessibility to ensure it is usable by people with disabilities.
© Copyright Building Research Establishment Ltd 2021
Comments
0 comments
Please sign in to leave a comment.