Aim
To encourage the monitoring of internal conditions to ensure a healthy indoor environment is provided.
Question
Are sensors installed in the asset that monitor the levels of carbon dioxide in indoor air?
Credits | Answer | Select a single answer |
0 | A | Question not answered |
0 | B | No |
2 | C | Yes, in areas subject to large and unpredictable or variable occupancy patterns |
4 | D | Yes, in areas subject to large and unpredictable or variable occupancy patterns and in all regularly occupied space |
Assessment criteria
Criterion | Assessment criteria | Applicable answer |
1 |
Carbon dioxide sensors are installed as follows:
|
C-D |
2 | Sensors must be installed, tested, calibrated and maintained in accordance with the manufacturer’s instructions. Sensors should be placed to provide representative readings of conditions within each space. Sensors should be wall-mounted and at a height above floor level that corresponds to an average seated or standing head height for the main activity performed within the space. | C-D |
Evidence
Criteria | Evidence requirement |
- | The evidence below is not exhaustive, please also refer to the ‘BREEAM evidential requirements’ section in the scope of the Guidance for appropriate evidence types which can be used to demonstrate compliance. |
All | Photographic evidence of the sensors. |
All | Description of how the sensors work in terms of actuating ventilation or alerting users. |
All | Operation and maintenance manuals or records for the installed system(s). |
Definitions
Areas with a large and unpredictable occupancy:
The following are examples of these types of spaces:
- Auditoria
- Gyms
- Retail stores or malls
- Cinemas
- Waiting rooms.
Occupied space:
A room or space within the asset that is likely to be occupied for 30 minutes or more by an asset user. For the purpose of this issue, the definition excludes the following:
- Atria or concourses
- Entrance halls or reception areas
- Ancillary space, e.g. circulation areas, storerooms and plant rooms.
Additional information
Set points for sensors
Table 16 provides guidance on appropriate set points for carbon dioxide sensors based on the recommendations in the European Technical Report ‘PD CEN/TR 16798-2:2019 Energy performance of buildings - Ventilation for buildings - Part 2: Interpretation of the requirements in EN 16798-1 – Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics (Module M1-6)’. This information is provided as guidance to inform Assessors and project teams of current industry practice on set points for sensors. The assessment criteria do not specify a target set point in order to allow building or facilities managers to select an appropriate set point for the asset’s ventilation system. However, set points should not exceed 1750 ppm and it is recommended that projects aim to achieve the Category II requirements as a minimum.
Table 16: Default design carbon dioxide concentrations
Note: The above values correspond to the equilibrium concentration when the air flow rate is 10, 7 and 4 litres per second per person for Category I, II, and III and IV, respectively; the carbon dioxide emission is 20 litres per hour per person; and assumes an average outdoor air carbon dioxide concentration of 400 ppm.
© Copyright Building Research Establishment Ltd 2021