(15 maximum points possible)
3.2.1 Vertical, Horizontal, and Inclined Transport Systems - Efficiency Measures (5 points)
GREEN GLOBES #3.2.1.1 - ANSI #8.4.1.1 Do building elevators use regenerative braking AND/OR machine-roomless (MRL) elevators for all passenger elevators and any regularly utilized elevators?
- Yes (2 points)
- No (0 points)
- N/A
Assessment Guidance
Not applicable where there are no elevators.
Recommended Documents
- Manufacturer’s specifications, cut sheets and performance documentation
- Drawings and specifications of vertical transport equipment
- Construction Documents
GREEN GLOBES #3.2.1.2 - ANSI #8.4.1.2 Are the following used to enhance the energy efficiency of elevator systems?
- TWIN elevators (stacked cabins on one operating elevator in one shaft)
AND/OR
- Elevators with a destination dispatch system (grouping people traveling to the same floor)
AND/OR
- Elevators with a zero-power sleep mode
- One or more of the prescribed strategies are used (1 points)
- There are no escalators or elevators (1 points)
- No (0 points)
Assessment Guidance
Per ANSI/GBI 01-2019 Green Globes Assessment Protocol for Commercial Buildings, one point is awarded where there are no escalators or elevators.
Recommended Documents
- Manufacturer’s specifications, cut sheets and performance documentation
- Drawings and specifications of vertical transport equipment
- Construction Documents
GREEN GLOBES #3.2.1.3 - ANSI #8.4.1.3 Do escalators and moving walkways have the capability to slow down or stop when detectors indicate no traffic or for the use of motor efficiency controllers?
- Yes (1 point)
- No (0 points)
- N/A
Assessment Guidance
Not applicable where there are no escalators or moving walkways.
Recommended Documents
- Manufacturer’s specifications, cut sheets and performance documentation
- Drawings and specifications of vertical transport equipment
- Construction Documents
GREEN GLOBES #3.2.1.4 - ANSI #8.4.1.4 Are one or more of the following energy efficient equipment systems related to the movement of people in use?
- Reclaim of Machine Room Waste Heat
AND/OR
- Linear Induction Motor (LIM)
AND/OR
- AC Synchronous Guide Rail hoisting motors with integral braking and controls
AND/OR
- Innovative energy efficient people-transport equipment or system (Requires statement of system description and benefits document for submittal)
- Yes (1 point)
- No (0 points)
- N/A
Assessment Guidance
Not applicable where the building does not contain any systems capable of using this equipment.
References
- Federal Energy Management Program’s (FEMP) Energy-Efficient Product Procurement
- ENERGY STAR Qualified Product Lists
Recommended Documents
- Manufacturer’s specifications, cut sheets and performance documentation
- Drawings and specifications of vertical transport equipment
- Descriptive explanation and technical definition document on the innovative solution used within the project
- Construction Documents
3.2.2 Local Shedding (5 points)
GREEN GLOBES #3.2.2.1 - ANSI #8.4.2.1 Are lighting systems installed that are capable of load shedding?
- Lighting systems can reduce power by equal to or greater than 30% from peak levels (3 points)
- Lighting systems can reduce power between 15% - 29% from peak levels (2 points)
- Lighting systems can reduce power by less than 15% (0 points)
- No (0 points)
Assessment Guidance
Loading shedding may be initiated automatically or manually.
GREEN GLOBES #3.2.2.2 - ANSI #8.4.2.2 Are HVAC equipment controls installed that are capable of load shedding?
- Yes (2 points)
- No (0 points)
Assessment Guidance
Loading shedding may be initiated automatically or manually. Load shedding program initiates setback of space temperatures, heating and cooling system hydronic temperatures, air system static pressure set-points, or cycling of heating and cooling equipment.
3.2.3 Plug Load and Process Energy Management (5 points)
GREEN GLOBES #3.2.3.1 - ANSI #8.4.3.1 Do project documents include an inventory of appliances and equipment organized by location?
- There is a complete inventory of expected plug load equipment appliances, and hard-wired process equipment (2 points)
- There is a complete inventory of hard-wired process equipment only (1 points)
- There is a complete inventory of plug load equipment and appliances only (1 points)
- No (0 points)
Assessment Guidance
The inventory must include:
- Nameplate power use;
- Typical power use; and
- An expected schedule of use
GREEN GLOBES #3.2.3.2 - ANSI #8.4.3.2 Is there an established policy requiring all new equipment purchases be based on energy efficient criteria, such as ENERGY STAR or other equivalent energy efficiency standards?
- Yes (1 point)
- No (0 points)
- N/A
Assessment Guidance
Not applicable if no equipment is subject to ENERGY STAR label criteria.
References
- Federal Energy Management Program’s (FEMP) Energy-Efficient Product Procurement
- ENERGY STAR Qualified Product Lists
GREEN GLOBES #3.2.3.3 - ANSI #8.4.3.3 Is the project furnished with receptacles that automatically control the availability of power based on occupancy sensors AND/OR timed schedules in accordance with ANSI/ASHRAE/IES Standard 90.1-2010?
- Energy-saving power strips are installed on ≥75% to 100% of private offices, open offices and computer classrooms (2 points)
- Energy-saving power strips are installed on ≥50% and < 75% of private offices, open offices and computer classrooms (1 points)
- Energy-saving power strips are installed on less than 50% of private offices, open offices and computer classrooms (0 points)
- No (0 points)
Assessment Guidance
This includes receptacles installed in modular partitions.
References