(2 points)
INTENT
Increase the supply of high-quality outdoor air and promote a connection to the outdoor environment by encouraging building users to open windows when outdoor air quality is acceptable.
SUMMARY
ISSUE
SOLUTIONS
IMPACT
REQUIREMENTS
Provide Operable Windows (1 point)
Verified by Architect, MEP, Photographic evidence
Note: Projects where the average outdoor PM2.5 level is 35 μg/m³ or higher may only achieve Part 1: Provide Operable Windows in conjunction with Part 2: Manage Window Use. The World Health Organization’s Global Urban Ambient Air Pollution Database may be consulted to view outdoor air quality levels, available at http://www.who.int/phe/health_topics/outdoorair/databases/cities/en/
The following requirements are met:
- Project meets one of the below:
- At least 75% of regularly occupied spaces have operable windows that provide access to outdoor air.
- The openable window area is equivalent to at least 4% of the net occupiable floor area of that space or floor plate.
- Project does not use radiant cooling systems if situated in climates with an annual relative humidity above 70%.
Manage Window Use (1 point)
Note: Projects may only receive points for this part if Part 1: Provide Operable Windows is also achieved.
The following requirements are met:
-
Outdoor levels of ozone, PM2.5 or PM10, and temperature are monitored at intervals of at least once per hour based on a data-gathering station located within 4 km [2.5 mi] of the building.
-
Data collected are made available to building occupants.
Indicator lights at windows and/or online notifications signal to regular building occupants when outdoor air allows for open windows based on when the following thresholds are met:
-
PM2.5 less than 15 μg/m³.
-
PM10 less than 50 μg/m³.
-
Dry-bulb temperature within 8 °C [15 °F] of indoor air temperature setpoint.
-
Ozone less than 51 ppb.
Apply Universal Design to Windows (1 point)
All operable windows in regularly occupied spaces comply with the following requirements:
-
Provide enough space to permit occupants to approach and operate them (from both a standing and seated position).
-
Are operable with one hand and with a closed fist and do not require tight grasping, pinching or twisting of the wrist.
-
Require less than 22 N [5 lbs] of force to open.