Required
Intent
To reduce indoor water consumption.
Requirements
Building Water Use
For the fixtures and fittings listed in Table 1, as applicable to the project scope, reduce aggregate water consumption by 20% from the baseline. Base calculations on the volumes and flow rates shown in Table 1.
All newly installed toilets, urinals, private lavatory faucets, and showerheads that are eligible for labeling must be WaterSense labeled (or a local equivalent for projects outside the U.S.).
Table 1. Baseline water consumption of fixtures and fittings
Commercial Fixtures, Fittings, and Appliances | Current Baseline (IP Units) | Current Baseline (SI units) |
---|---|---|
Water closets (toilets)* | 1.6 gallons per flush (gpf) | 6 liters per flush (lpf) |
Urinal* | 1.0 (gpf) | 3.8 lpf |
Public lavatory (restroom) faucet | 0.5 gpm at 60 psi all others except private applications | 1.9 lpm at 415 kPa, all others except private applications |
Private lavatory faucet* | 2.2 gpm at 60 psi | 8.3 lpm at 415 kPa |
Kitchen faucet (excluding faucets used exclusively for filling operations) | 2.2 gpm at 60 psi | 8.3 lpm at 415 kPa |
Showerhead* | 2.5 gpm at 80 psi per shower stall | 9.5 lpm at 550 kPa per shower stall |
* WaterSense label available for this product type gpf = gallons per flush gpm = gallons per minute psi = pounds per square inch lpf = liters per flush lpm = liters per minute kPa = kilopascals |
Appliance and Process Water Use
Install appliances, equipment, and processes within the project scope that meet the requirements listed in the tables below.
Existing appliances intended for reuse in the project are not required to meet the requirements in Table 2.
Table 2. Standards for appliances
Appliance | Requirement |
---|---|
Residential clothes washers | ENERGY STAR or performance equivalent |
Commercial clothes washers | ENERGY STAR or performance equivalent |
Residential dishwashers (standard and compact) | ENERGY STAR or performance equivalent |
Prerinse spray valves | ≤ 1.3 gpm (4.9 lpm) |
Ice machine | ENERGY STAR or performance equivalent and use either air-cooled or closed-loop cooling, such as chilled or condenser water system |
gpm = gallons per minute
lpm = liters per minute
Table 3. Standards for processes
Process | Requirement |
---|---|
Heat rejection and cooling | No once-through cooling with potable water for any equipment or appliances that reject heat |
Cooling towers and evaporative condensers | Equip with:
|