(1-2 points)
Intent
To minimize waste of energy caused by uncontrolled air leakage into and from conditioned spaces.
Requirements
Case 1. Single Family
Meet the air leakage requirements shown in Table 1 or Table 2.
Case 2. Multifamily
Meet the air leakage requirements shown in Table 1 or Table 2.
Meet the requirements for leakage to outside the conditioned envelope for each dwelling unit, unless the whole building can be entirely and sufficiently depressurized by a blower door(s).
Table 1. Points for reducing air leakage, in ACH50
Table 2a. Points for reducing air leakage, in cfm50 per sf envelope area
Performance requirements IECC climate zone |
Points | |||
---|---|---|---|---|
1–2 | 3–4 | 5–7 | 8 | |
.195 | .16 | .125 | .0925 | 1 |
.1375 | .115 | .0925 | .0675 | 2 |
Table 2b. Points for reducing air leakage, in cmm50 per 100 square meter envelope area
Performance requirements IECC climate zone |
|||||
---|---|---|---|---|---|
1–2 | 3–4 | 5–7 | 8 | Points | |
5.94 | 4.87 | 3.81 | 2.82 | 1 | |
4.19 | 3.50 | 2.82 | 2.06 | 2 |
cfm = cubic feet per minute
ELR = envelope leakage ratio
IECC = International Energy Conservation Code
sf = square feet
cmm = cubic meters per minute
Credit only available for projects using the EA prescriptive path’
© Copyright U.S. Green Building Council, Inc. All rights reserved.